CAN (Controller Area Network) is a serial bus system especially
suited to structure intelligent industry devices networks and build smart automatic
control systems. The following figure shows the application architecture for I-7530A
modules. The PC can be the CAN host, monitor or HMI to access/control the CAN device
through the CAN network by the I-7530A Converter.
The programmable RS-232/485/422
device (For example: I-8411/I-8431/I-8811/I-8831/W-8031/W-8331/W-8731 embedded controller)
can use the serial port to connect to the CAN network via the I-7530A module. In
order to use the CAN network with traditional RS-232/485/422 devices, we provide
a way to achieve this purpose. The I-7530A is designed to unleash the power of CAN
bus via RS-232/485/422 communication method. It accurately converts messages between
CAN and RS-232/485/422 networks. This module let you to communicate with CAN devices
easily from any PC or devices with RS-232/485/422 interface.
Moreover, we expand the functionalities of I-7530A for some special application.
In pair connection mode, I-7530A can be used to connect PC with other RS-232/485/422
devices at the same time. The application architecture may be as follows.
3000V isolation on CAN side
The CAN port of I-7530A is an isolated with 3000V isolation. This isolation can
protect the local RS-232/485/422 devices from the damage signal coming from CAN
network.
Watchdog inside
The I-7530A Watchdog is a hardware reset circuit to monitor the I-7530A’s operation
status. When working in harsh or noisy environment, the I-7530A may be down by the
external signal. The circuit may let the I-7530A to work continuously and never
halt.
Power and Error indicator display
There are two indicators on the I-7530A.The power indicator can help user to check
whether the I-7530A is standby or transmitting/receiving messages. The Error indicator
will be turned on when some errors occur on the I-7530A.
Features
Compatible with CAN specification 2.0A and B
Fully compatible with ISO 11898-2 standard
Support various bauds from 10K bps to 1M bps
Jumper for 120 Ω terminator resistor
Software configurable CAN and RS-232 /422/485 communication parameters
Power, data flow and error indicator for CAN and RS-232/422/485
Watchdog inside
Provide the transparent communication between the RS-232/485/422 devices via CAN bus
Enable different RS-232/485/422 devices into an individual group in CAN bus network.
(Full-duplex communication mode of RS-232/422 devices is not supported)
Software Utility Features
CAN bus Baud rate configuration
CAN acceptance filter configuration
CAN 2.0A or 2.0B specific selection
RS-232/485/422 Baud rate and data bit setting
RS-232/485/422 responded selection
Easy test to transmit/receive CAN messages
Setting for I-7530A communication mode (normal mode or pair connection mode)
CAN Monitor & Datalog Tool
t has a CAN message field which can display the receiving CAN messages in Decimal or HEX mode.
Can display the timestamp of each received CAN message.
Users can change the display mode, up-down, down-up or stop.
It can count the number of received CAN messages.
Data Log : It can save the CAN message as “ txt ” file.
Has CAN ID filter function.
Can send CAN message to CAN BUS according the defined interval time.
Product specification
CAN Interface
Controller
Microprocessor inside with 20MHz
Transceiver
NXP 82C250
Connector
9-pin male D-Sub (CAN_L, CAN_SHLD, CAN_H, N/A for others)
Port Channels
1
Buad Rate
10 k, 20 k, 50 k, 100 k, 125 k, 250 k, 500 k, 800 k and 1 Mbps
Protection
3000 VDC power protection on CAN side, 2500Vrms photo-couple isolation on CAN bus