Product specification |
Model | KIEN5000 |
Description | Managed Industrial ETHERNET Rail Switch,store and forward switchingmode, Ethernet (10 Mbit/s) and Fast-Ethernet (100 Mbit/s) |
Port Type and Quantity | 4x 100Mbit/s, TP cable, redundant, Auto-Negotiation 4 x 10/100Base-T/TX, TP cable, RJ45 socket (shielded), Auto-Negotiation |
More Interface |
Power Terminal | 2x DC power terminal, 3-core |
Alarm Terminal | 1 x alarm output terminal, 2-core |
RS232 interface | 1x RJ45 socket |
Network size-length of cable |
Twisted pair (TP) | 100m |
Network size - cascadibility |
Line - / star topology | Any |
Ring structure (DT-Ring) | 50 switches (recovery time < 300ms) |
Power requirements |
Power input | DC 18V~36V redundant power supply |
Power consumption | «8W |
Performance |
Transfer Rate | 148810pps |
MAC Address Table Size | 1K |
Service |
Diagnostics | LEDs (power, link status, port rate,management status), fault relais (24VDC/1A) |
Configuration | Web page, Telnet, Console |
Security | Port security (MAC based and IP based) |
Other services | Prioritization (IEEE 802.1D/p), VLAN(802.1Q), multicast (IGMPsnooping/querier, GMRP), broadcastlimite, flow control (IEEE802.3x) |
Redundancy |
Redundancy functions | DT-Ring (ring structure), STP (spanning tree protocol), redundant 24Vpower supply |
Ambient conditions |
Operating temperature | -35°C to +75°C |
Storage/transport temperature | -45°C to +85°C |
Relative humidity (non-condensing) | 10% to 95% |
MTBF | 10 years |
Mechanical construction |
Dimensions (W x H x D) | 55.4mm x 142mm x 120.5mm |
Mounting | DIN-Rail or Wall mounting |
Protection class | IP40 |
EMC interference immunity |
EN 61000-4-2 electrostatic discharge (ESD) | +4 kV contact discharge, +8kV air discharge |
EN 61000-4-3 electromagnetic field | 10 V/m (80 - 1000 MHz) |
EN 61000-4-4 fast transients (burst) | +2 KV power line, +1kV data line |
EN 61000-4-5 surge voltage | Power line: +2 kV(line/earth), +1 kV (line/line), +1kV data line |
EN 61000-4-6 conducted immunity | 3 V (10 kHz - 150 kHz), 10 V (150 kHz - 80MHz) |
EMC emitted immunity |
FCC CFR47 Part 15 | FCC CFR47 Part 15 Class A |
EN 55022 | EN 55022 Class A |
Approvals |
Certificate | FCC, CE, UL |