ViewPAC series VP-2117 is the ISaGRAF PAC with graphic display and keypad. It is equipped with an 80186 CPU (16-bit and 80 MHz) running a MiniOS7 operating system, 3 I/O slots, a STN LCD, a rubber keypad and various connectivity including Ethernet and RS-232/485.
Its operating system, MiniOS7, can boot up in a very short time (0.4 ~ 0.8 seconds). It has a built-in hardware diagnostic function, and supports the full range of functions required to access all high profile I-8K and I-87K series I/O modules, such as DI, DO, DI/DO, AI, AO, Counter/Frequency, motion control modules, etc. Users can also choose RS-485 Remote I/O modules (I-7000 series) or expansion units (RU-87Pn or I-87Kn) plugged with high profile I-87K serial I/O modules.
Compared with traditional HMI + PLC solutions, ViewPAC reduces overall system cost, space and gives you all the best features of HMIs and PLCs.
All remote I-7000 and I-87K DI modules support counters. 100 Hz max. value: 0 ~ 65535
High Speed Counter
I-87082W: 100 kHz max. 32 bit
I-8084W: 250 kHz max. 32 bit
Encoder
I-8093W: 3-axis Encoder Module, max. 1M Hz for quadrant input mode, max. 4M Hz for
pulse/direction and cw/ccw input mode. (FAQ-112)
I-8084W: 250 kHz max., 4-ch encoder, can be pulse/direction, or Up/Down or A/B phase
(Quad. mode) Not support Encoder Z-index. (FAQ-100)
Up to 2 COM Ports (COM1 ~ 3 and COM5 if multi-serial port boards are plugged in)can support Modbus RTU Master or ASCII Master protocol to connect to other Modbus Slave devices, 2 ports support up to 128 Modbus_xxx function blocks (same type).
Modbus RTU Slave
Protocol
Up to 2 COM Ports, COM1 and one of (COM2, COM3) can support Modbus RTU Slave protocol for connecting ISaGRAF, PC/HMI/OPC Server and MMI panels.
Modbus TCP/IP Slave
Protocol
Support Modbus TCP/IP Slave protocol for connecting ISaGRAF and PC/HMI. (Max. 6 connections)
Remote I/O
One of COM2, 3 supports I-7000 I/O modules and (I-87K base or RU-87P1/2/4/8) + I-87K High Profile I/O cards as Remote I/O. Max. 64 Remote I/O module for one controller
Fbus
Built-in COM3 Port to exchange data between ICP DAS's ISaGRAF PACs.
Ebus
To exchange data between ICP DAS's ISaGRAF Ethernet PACs via Ethernet port.
SMS:
Short Message Service
One of COM3 or (COM5 in multi serial port board) can link to a GSM modem to support SMS. User can request data/control the controller by cellular phone. The controller can also send data and alarms to user's cellular phone. Optional GSM/GPRS modem: GTM-201-RS232 (850/900/1800/1900 GSM/GPRS External Modem) or visit to http://www.icpdas.com/products/GSM_GPRS/wireless/GSM_GPRS_modem.htm for recommended GSM/GPRS modem.
User-defined Protocol
User can write his own protocol applied at COM1 ~ COM3 ( and COM5 ~ COM16 if multi-serial port boards are plugged) by serial communication function blocks.
CAN/CANopen
Up to 3 COM Port. User can use its COM1, 3, or (COM5 ~ COM12, resides at the I-8112iW/8114W/
8114iW RS-232 expansion board) to connect one I-7530 (RS-232 to CAN converter) to support CAN/CANopen devices and sensors. One VP-2117 supports max. 3 RS-232 Ports to connect max. 3
I-7530. Please refer to www.icpdas.com FAQ Software ISaGRAF Ver.3 (English) FAQ-086.
FRnet I/O
Support Max. 3 I-8172W FRnet Master cards to connect FRnet I/O modules. (Max. 768-ch. DI +
768-ch. DO)
Sending E-mail
Actively or passively sending E-mail via Ethernet port through internet. Max.10 receivers for each sending and can send E-mail with an attached file. (Max. file size is about 488 KB)