Tabelka poniżej prezentuje parametry techniczne urządzenia. W przypadku, gdyby prezentowane w niej informacje były niekompletne lub budziły wątpliwości prosimy o kontakt mailem bądź telefonicznie z naszym działem technicznym. Dodatkowo służymy pomocą w doborze właściwego urządzenia tak, aby optymalnie spełniało wymagania Państwa projektu.
Specification
Development Software
ISaGRAF Software
ISaGRAF Version 3 : IEC 61131-3 standard. Languages: LD, ST, FBD, SFC, IL & FC
Yes, with one power relay (1 A @ 24 VDC) for alarm.
Capacity
iP-8447: 0.85 A, 5 V supply to CPU; 5.51 A, 5 V supply to I/O expansion slots, total 30 W.
iP-8847: 0.9 A, 5 V supply to CPU; 5.1 A, 5 V supply to I/O expansion slots, total 30 W.
Consumption
iP-8447: 6.7 W (0.28 A @ 24 V), iP-8847: 7.2 W (0.3 A @ 24 V)
General Environment
Temperature
Operating : -25 ~ +75 C
Storage : -30 ~ +85 C
Humidity
5 ~ 95 % RH (non-condensing )
System
CPU
80186, 80 MHz (16-bit) or compatible.
Watchdog Timer
Yes, Default = 0.8 second
RTC (Real Time Clock)
Provide seconds, minutes, hours, day of week/month, month and year, valid from 1980 to 2079.
SRAM
768 KB
Dual Battery Backup SRAM
512 KB (for 5 years data retention), support up to 1024 retain variables.
FLASH Memory
512 KB, 100,000 erase/write cycles with Flash protection switch.
NVRAM
31 bytes, battery backup, data valid up to 5 years.
Yes, on the front panel. 4 push buttons, 3 green programmable LEDs, 1 red power LED and 5-digit 7-Seg. LED (Display message, value, input value, simulate input & output.)
NET ID
8-pin DIP switch to set NET ID as 1 ~ 255.
I/O Expansion Slots
Slot Number
iP-8447: 4 empty slots, iP-8847: 8 empty slots. For high profile parallel (I-8K) & serial (I-87K) I/O boards.
Hot-Swap
Support Hot-Swap I-87K high profile I/O module on the slot 0~7 if the module needs to be replaced.
RS-232: TxD,RxD,RTS,CTS,DSR,DTR,CD,RI,GND. Speed: 115200 bps max. Full modem signals.
Motion Control
Can integrate with one I-8091W (2-axis) or two I-8091W (4-axis) to do motion control. Ethernet communication is also available when doing motion control.
I-8093W : 3-axis Encoder Module, max. 1M Hz for quadrant input mode, max. 4M Hz for pulse/direction and cw/ccw input mode. (FAQ-112)
I-8084W: 250 kHz max. , 4-ch encoder, can be Dir/Pulse, or Up/Down or A/B phase (Quad. mode); Not support Encoder Z-index. (FAQ-100)
Up to 2 COM Ports, COM1 ~ (COM5 in multi serial port board) can support Modbus RTU Master or ASCII Master protocol to connect to other Modbus Slave devices. Max. Modbus_xxx Function Block amount for 2 ports: 128.
Modbus Slave Protocol
Up to 2 COM Ports, COM1 and one of (COM2, COM3) can support Modbus RTU Slave protocol for connecting ISaGRAF, PC/HMI/OPC Server & MMI panels.
Modbus TCP/IP Protocol
2 Ethernet ports support Modbus TCP/IP Slave Protocol for connecting ISaGRAF & PC/HMI. (Max. 6 connections)
Remote I/O
One of COM2 or COM3 or COM4 supports I-7000 I/O modules & [(I-87Kn base or RU-87P1/2/4/8)+ I-87K High Profile I/O boards] as Remote I/O. Max. 64 Remote I/O module for one PAC.
Fbus
Built-in COM3 Port to exchange data between ICP DAS’s ISaGRAF PACs.
Ebus
To exchange data between ICP DAS’s ISaGRAF Ethernet PACs via Ethernet port. (The LAN2: upper port ONLY)
SMS:
Short Message Service
One of COM4 or (COM5 in multi serial port board) can link to a GSM modem to support SMS. User can request data/control the controller by cellular phone. The controller can also send data & alarms to user’s cellular phone. Optional GSM/GPRS modem: GTM-201-RS232 (850/900/1800/1900 GSM/GPRS External Modem) or visit to http://www.icpdas.com/products/GSM_GPRS/wireless/GSM_GPRS_modem.htm for recommended GSM/GPRS modem.
User-defined Protocol
User can write his own protocol applied at COM1, COM2, COM3, COM4 (& COM5 ~ COM20 if multi-serial port boards are plugged) by serial communication function blocks.
Modem_Link
COM4 can connect a general Modem. Supports PC to remotely download & monitor the controller.
MMICON/LCD
One of COM3 or COM4 supports ICP DAS’s MMICON. The MMICON is featured with a 240 x 64 dot LCD and a 4 x 4 Keyboard. User can use it to display picture, string, integer, float, and input a character, string, integer and float.
Redundant Bus7000
Two ISaGRAF PACs can link to remote I-7000 & I-87K High profile I/O modules at the same time. Only one controller is active to control these Remote I/Os. If one is dead, the other one will take over the control of Remote I/Os.
CAN/CANopen
iP-8x47 can use its COM1,3,4 or (COM5 ~ COM12 resides at the I-8112iW/8114W/8114iW RS-232 expansion board) to connect one I-7530 : the RS-232 to CAN converter to support CAN and CANopen devices and sensors. One iP-8x47 supports max.3 RS-232 ports to connect max.3 I-7530. Please refer to www.icpdas.com > FAQ > Software > ISaGRAF Ver.3 (English) FAQ-086.
FRnet I/O
Support Max.4 I-8172W FRnet Master cards to connect FRnet I/O modules. (Max. 1024-ch. DI + 1024-ch. DO)
Sending E-mail
Actively or passively sending E-mail via Ethernet port through internet. Max.10 receivers for each sending and can send
E-mail with an attached file. (Max. file size is about 488 KB)