Tabelka poniżej prezentuje parametry techniczne urządzenia. W przypadku, gdyby prezentowane w niej informacje były niekompletne lub budziły wątpliwości prosimy o kontakt mailem bądź telefonicznie z naszym działem technicznym. Dodatkowo służymy pomocą w doborze właściwego urządzenia tak, aby optymalnie spełniało wymagania Państwa projektu.
| Product specification |
| Input |
| Voltage range |
85 ~ 264 VAC 120 ~ 370 VDC |
| Frequency range |
47 ~ 63Hz |
| Efficiency (Typ.) |
84% |
| AC Current (Typ.) |
0.55 A/115 VAC 0.35 A/230 VAC |
| Inrush Current (Typ.) |
COLD START 20
A/115 VAC 40 A/230 VAC |
| Leakage current |
less than 1 mA / 240 VAC |
| Output |
| DC Voltage |
24 VDC |
| Rated Current |
1 A |
| Current Range |
0 ~ 1 A |
| Rated power |
24 W |
| Ripple and noise (max.)Note.2 |
150mVp-p |
| Voltage ADJ.
range |
21.6 ~ 26.4 V |
| Voltage
Tolerance Note.3 |
1.0% |
| Line Regulation |
1.0% |
| Load regulation |
1.0% |
| Setup, rise Time
Note.5 |
50 ms/230 VAC 0 ms/115 VAC
at full load |
| Hold up time
(Typ.) |
85 ~ 264 VAC 120 ~ 370 VDC |
| Protection |
| Overload |
105 ~ 160% rated output
power Protection type : Constant current limiting, recovers automatically
after fault condition is removed |
| Over voltage |
27.6 ~ 32.4V Protection type : Shut down o/p voltage, re-power on to recover |
| Function |
| DC OK Active Signal (max.) |
18 ~ 27 V/20 mA |
| Environmental |
| Working temp. |
-20 ~ +70C (Refer
to output load derating curve) |
| Working humidity |
20 ~ 90% RH
non-condensing |
| Storage TEMP., humidity |
-40 ~ +85C , 10
~ 95% RH |
| TEMP. Coefficient |
0.03%/C (0 ~
50C) |
| Vibration |
Component:10 ~
500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes Mounting:
Compliance to IEC60068-2-6 |
| Safety and EMC (Note 4) |
| Safety
standards |
UL508, TUV
EN60950-1 approved, NEC class 2 / LPS compliant |
| Withstand
voltage |
I/P-O/P:3KVACI/P-FG:1.5KVACO/P-FG:0.5KVAC |
| Isolation
resistance |
I/P-O/P,
I/P-FG, O/P-FG:100M Ohms/500VDC |
| EMI
Conduction and Radiation |
Compliance
to EN55011,EN55022 (CISPR22), EN61204-3 Class |
| Hsrmonic
current |
Compliance
to EN61000-3-2,-3 |
| EMS
immunity |
Compliance
to EN61000-4-2, 3, 4, 5, 6, 8, 11, ENV50204,
EN55024,EN61000-6-1,EN61204-3, light industry level, criteria A |
| Others |
| MTBF |
236.9K hrs
min. MIL-HDBK-217F (25C ) |
| Dimension
(WxHxD) |
22.5mm x
90mm x 100mm |
| Packing |
0.19Kg
72pcs/14.7Kg/0.91CUFT |