Tabelka poniżej prezentuje parametry techniczne urządzenia. W przypadku, gdyby prezentowane w niej informacje były niekompletne lub budziły wątpliwości prosimy o kontakt mailem bądź telefonicznie z naszym działem technicznym. Dodatkowo służymy pomocą w doborze właściwego urządzenia tak, aby optymalnie spełniało wymagania Państwa projektu.
Product specification
Input
Voltage range
85 ~ 264VAC
120 ~ 370VDC
Frequency range
47 ~ 63Hz
Efficiency (Typ.)
88%
AC Current (Typ.)
1.8A/115VAC
1A/230VAC
Inrush Current (Typ.)
Cold Start 30A/115VAC
60A/230VAC
Leakage current
less than 1mA / 240VAC
Output
DC Voltage
24V
Rated Current
2.5A
Current Range
0 ~ 2.5A
Rated power
60W
Ripple and noise (max.) Note.2
150mVp-p
Voltage ADJ. range
24 ~ 30V
Voltage Tolerance Note.3
1.0%
Line Regulation
1.0%
Load regulation
1.0%
Setup, rise Time Note.5
500ms, 30ms/230VAC
500ms, 30ms/115VAC at full load
Hold up time (Typ.)
50ms/230VAC
20ms/115VAC at full load
Protection
Overload
105 ~ 150% rated output power Protection type : Constant current limiting, recovers automatically after fault condition is removed
Over voltage
31.2 ~ 36V Protection type : Shut down o/p voltage, re-power on to recover
Function
DC OK signal
Relay contact rating(max.): 30V/1A resistive
Environmental
Working temp.
-20 ~ +70C (Refer to output load derating curve)
Working humidity
20 ~ 90% RH non-condensing
Storage TEMP., humidity
-40 ~ +85C , 10 ~ 95% RH
TEMP. Coefficient
0.03%/C (0 ~ 50C)
Vibration
Component : each along X, Y, Z axes
Mounting : Compliance to IEC60068-2-6 10 ~ 500Hz, 2G 10min./1cycle, period for 60min.
Safety and EMC (Note 4)
Safety standards
UL508, TUV EN60950-1 approved, NEC class 2 / LPS compliant (24V,48V only)
Withstand voltage
I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC
Isolation resistance
I/P-O/P, I/P-FG, O/P-FG: more than 100M Ohms/500VDC 25C 70%RH
EMI Conduction and Radiation
Compliance to EN55011, EN55022 (CISPR22), EN61204-3 Class B
Hsrmonic current
Compliance to EN61000-3-2,-3
EMS immunity
Compliance to EN61000-4-2, 3, 4, 5, 6, 8, 11, ENV50204, EN55024, EN61000-6-2, EN61204-3, heavy industry level, criteria A
DC OK Relay Contact
Contact Close
When the output voltage reaches the adjusted output voltage.
Contact Open
When the output voltage drop below 90% output voltage.